CONSUMO DEL CABLEADO

Is = 5A1m2m3m4m5m6m7m8m9m10m
1.5mm20.61.191.792.382.983.574.174.765.365.95
2.5mm20.360.711.071.431.782.142.52.863.213.57
4mm20.220.450.670.891.121.341.561.792.012.24
6mm20.150.30.450.60.740.891.041.191.341.49
10mm20.090.180.270.360.440.540.630.710.80.89

Perdidas en VA. Las distancias se expresan en metros dobles

Is = 1A10m20m30m40m50m60m70m80m90m100m
1.5mm20.240.480.720.961.191.431.671.912.152.38
2.5mm20.140.290.430.570.720.8611.141.291.43
4mm20.090.180.270.360.450.540.630.710.80.89
6mm20.060.120.180.240.30.360.420.480.540.6
10mm20.040.070.110.140.180.210.250.290.320.36

Perdidas en VA. Las distancias se expresan en metros dobles