Accuracy of current transformers

As per IEC 61869 “Instrument transformers – current transformers”

Accuracy classError 0,05InError 0,2InError 0,5InError InError 1,2In
0,10,4%0,2%–0,1%0,1%
0,20,75%0,35%–0,2%0,2%
0,51,5%0,75%–0,5%0,5%
13%1,5%–1%1%
3––3%–3%

Ratio errors accuracy classes

Accuracy classPhase displ. 0,05InPhase displ. 0,2InPhase displ. InPhase displ. 1,2In
0,115′8′5′5′
0,230′15′10′10′
0,590′45′30′30′
1180′90′60′60′
3––––

Phase displacement accuracy classes

Accuracy classError 0,01InError 0,05In Error 0,2InError InError 1,2InComposite error at rated accuracy limit current
0,2S0,75%0,35%0,2%0,2%0,2%–
0,5S1,5%0,75%0,5%0,5%0,5%–
5P–––1%–5%
10P–––3%–10%

Ratio errors classes S and protection

Accuracy classPhase displ. 0,01InPhase displ. 0,05InPhase displ. 0,2InPhase displ. InPhase displ. 1,2In
0,2S30′15′10′10′10′
0,5S90′45′30′30′30′
5P–––60′–
10P–––––

Phase displacement classes S and protection