Accuracy of current transformers
As per IEC 61869 “Instrument transformers – current transformers”
Accuracy class | Error 0,05In | Error 0,2In | Error 0,5In | Error In | Error 1,2In |
0,1 | 0,4% | 0,2% | – | 0,1% | 0,1% |
0,2 | 0,75% | 0,35% | – | 0,2% | 0,2% |
0,5 | 1,5% | 0,75% | – | 0,5% | 0,5% |
1 | 3% | 1,5% | – | 1% | 1% |
3 | – | – | 3% | – | 3% |
Ratio errors accuracy classes
Accuracy class | Phase displ. 0,05In | Phase displ. 0,2In | Phase displ. In | Phase displ. 1,2In |
0,1 | 15′ | 8′ | 5′ | 5′ |
0,2 | 30′ | 15′ | 10′ | 10′ |
0,5 | 90′ | 45′ | 30′ | 30′ |
1 | 180′ | 90′ | 60′ | 60′ |
3 | – | – | – | – |
Phase displacement accuracy classes
Accuracy class | Error 0,01In | Error 0,05In | Error 0,2In | Error In | Error 1,2In | Composite error at rated accuracy limit current |
0,2S | 0,75% | 0,35% | 0,2% | 0,2% | 0,2% | – |
0,5S | 1,5% | 0,75% | 0,5% | 0,5% | 0,5% | – |
5P | – | – | – | 1% | – | 5% |
10P | – | – | – | 3% | – | 10% |
Ratio errors classes S and protection
Accuracy class | Phase displ. 0,01In | Phase displ. 0,05In | Phase displ. 0,2In | Phase displ. In | Phase displ. 1,2In |
0,2S | 30′ | 15′ | 10′ | 10′ | 10′ |
0,5S | 90′ | 45′ | 30′ | 30′ | 30′ |
5P | – | – | – | 60′ | – |
10P | – | – | – | – | – |
Phase displacement classes S and protection