Permissible current in a busbar
Ambient temperature = 30°C
Maximum busbar temperature rise = 40°C
Bars on edge
Busbar spacing equal to thicknes of 1 bar
Permissible current in Amps
Bar | Copper | Copper | Copper | Copper | Aluminium | Aluminium | Aluminium | Aluminium |
size (mm) | 1 bar | 2 bars | 3 bars | 4 bars | 1 bar | 2 bars | 3 bars | 4 bars |
20 x 5 | 320 | 570 | 730 | 940 | 190 | 340 | 430 | 570 |
30 x 5 | 460 | 820 | 1050 | 1380 | 360 | 640 | 820 | 1080 |
40 x 5 | 550 | 990 | 1260 | 1650 | 430 | 770 | 980 | 1290 |
50 x 5 | 650 | 1170 | 1490 | 1950 | 510 | 910 | 1170 | 1530 |
60 x 5 | 840 | 1510 | 1930 | 2520 | 660 | 1180 | 1510 | 1980 |
80 x 5 | 1000 | 1800 | 2300 | 3000 | 780 | 1400 | 1790 | 2340 |
100 x 5 | 1200 | 2160 | 2760 | 3600 | 940 | 1690 | 2160 | 2820 |
160 x 5 | 1800 | 3240 | 4140 | 5400 | 1410 | 2530 | 3240 | 4230 |
Current in a busbar